Product Overview
GGD AC low-voltage power distribution cabinets are used in power users such as power plants, substatories, factories and mines, etc. In power distribution systems with an AC frequency of 50-60Hz, a rated operating voltage of 380 V and a rated operating current up to 3150A, they are used for power conversion, distribution and control of power, lighting and power distribution equipment.
The GGD type AC low-voltage power distribution cabinet is a new type of low-voltage power distribution cabinet designed in accordance with the requirements of the majority of power users and design departments of the Ministry of Energy, following the principles of safety, economy, rationality and reliability. The product features high breaking capacity, excellent dynamic and thermal stability, flexible electrical schemes, convenient combination, strong serialization and practicability, novel structure and high protection grade. It can be used as a replacement product for low-voltage complete switchgear.
GGD type AC low-voltage power distribution cabinets comply with national and industrial standards.

Usage Environment
1.The ambient air temperature shall not be higher than +40℃ and not lower than -5℃, and the average temperature within 24 hours shall not be higher than +35℃.
2. For indoor installation and use, the altitude of the place of use shall not exceed 2000m.
3. The relative humidity of the ambient air shall not exceed 50% at the maximum temperature of +40℃. Higher relative humidity is permitted at lower temperatures, for example, 90% at +20℃.
Consideration shall be given to the possible occasional condensation caused by temperature changes.
4. Pollution degree 3.
5. The inclination of the equipment relative to the vertical plane during installation shall not exceed 5°.
6. The equipment shall be installed in a place free from severe vibration and impact, as well as in an environment where electrical components will not be corroded.
Technical Parameters
| Item | Unit | Parameter | |
| Rated Voltage | V | AC380 | |
| Rated Frequency | HZ | 50 | |
| Rated Current | Maximum operating current of the horizontal busbar | A | ≤ 4000 |
| Maximum operating current of vertical busbars | 800、1600 | ||
| Rated Short-Time Withstand Current (1s) | kA | 15、30、50 | |
| Rated Peak Withstand Current | kA | 30、63、105 | |
| dielectric strength | V/1min | 2500 | |
| rated insulation voltage | V | 660 | |
| Protection Level | IP30/IP40 | ||
| Dimensions(Width ×Depth × Height) | mm | 600(800、1000)×600(800、1000)×2200 | |
Our Advantages
1.Quick quotations and electrical design services available.
2.Short delivery time, with the fastest delivery cycle being 20 working days.
3.Comprehensive after-sales service system, ensuring worry-free purchases for customers.
4.Authoritative product certifications: ISO, CCC, etc.
5.Complete quality management system to ensure product quality.
Ordering Guide
The customer needs to provide the following information:
A. Main circuit schematic, secondary circuit system diagram, and auxiliary circuit control method.
B. Equipment layout diagram and distribution room floor plan.
C. Inlet and outlet wiring method. If busbar bridges are required between equipment, please provide data such as busbar spacing and height above the ground.
D. Any other special requirements can be discussed with our company.